As more and more electronic equipment is connected to the Power Supply Network the effect of non-linear loads will cause deterioration in quality. The introduced Engineering Recommendation G5/4 lays down the conditions under which connection to the Electricity Supply Network will be allowed and affect every consumer connected to the public electricity supply, including domestic and commercial consumers, as well as industrial users.
 
Halcyon Drives can offer a comprehensive service to enable our customers to ascertain the quality of their power supply both before and after connection of non-linear loads.

Site Surveys
A Site Survey for the purpose of establishing the present levels of Harmonic Distortion can be carried out and would include:
 
  1. ASSESSMENT OF EXISTING SITE CONDITIONS
    To conduct a Harmonic Survey it is necessary to establish the present site conditions. This includes investigation of the supply transformers; establishment of the Point of Common Coupling (PCC); assessment of the single line distribution including pertinent ancillary equipment such as Power Factor Correction equipment; method of connection of the monitoring equipment.

  2. CONNECTION OF MONITORING EQUIPMENT
    Site visit to connect the Monitoring Equipment.

  3. DISCONNECTION OF EQUIPMENT
    Site visit to disconnect monitoring equipment after a pre-determined monitoring period.


  4. PRODUCE A REPORT OF THE FINDINGS
    To include all information required under G5/4, an associated computer program would be used to interpret current site results and predicted harmonic levels will confirm a customer solution to ensure current legislation compliance can be achieved.
At the request of one of our customers, the charts below show the measurements made to check the levels of distortion prior to the installation of three variable speed drives rated 90KW. The drives will be operated in duty / assist / standby mode.
Pre-installation Harmonic Results Post-installation Harmonic Results
Fig 1
  Fig 2Click for larger image
Shows the results of an on-site harmonic survey undertaken by Halcyon Drives before the fitting of the three drives.
As a result of the high level of distortion recorded primarily in the 5th harmonic, which would be worsened by the installation & operation of these drives, Halcyon Drives recommended the fitting of a power quality filter manufactured by ABB.
 Demonstrates the recorded increase in harmonic distortion after the operation of the new drives until the switch-on of the Halcyon Drives supplied power quality filter on the 13 May. The power quality filter significantly reduces the harmonic currents fed into the supply from the drives.